Roland R-1000 Instrukcja Obsługi Strona 91

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 136
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 90
Manual
Double Sheet Detector R1000 series E20
B0046991 / Rev. 1.6
Communication with the PLC
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
91
6.3.6 External Teach-In (via PLC inputs)
This function may be required for special applications. It is, however, switched off in the standard
factory adjustment. If required it can be activated according chapter “7. Start-up“.
Note During Teach-In one sheet of nominal thickness must be placed in
front of the sensor.
Note A zero adjust procedure must be executed immediately before the
Teach-in procedure.
OUT0
IN0-1, 3-10
Enable
1
> 30ms
2
OUT3
OUT2
IN2
Teach-In
3
4
< 30ms
5
> 30ms
OUT1
6
< 7 sec.
0-sheet
1-sheet
2-sheet
Przeglądanie stron 90
1 2 ... 86 87 88 89 90 91 92 93 94 95 96 ... 135 136

Komentarze do niniejszej Instrukcji

Brak uwag